Answer: 

Section 535.228(c)(3)(D) of the Standards of Practice requires inspectors to report as deficient deficiencies in flashing details. Drip and rake edge flashing materials are recommended by most shingle manufacturers but are not required. If installed and if visible, the installation described in your question is required to be reported as a deficiency. However, the inspector is not required to inspect every inch of the material under the roof and may “spot check” for this condition.